Environment
 
New
    LPT Low Power Transmitter
CRLPTTCO-0

LPT Low Power Transmitter

Single channel, analog gas detector for enclosed parking facilities, recreational facilities, oxygen depletion applications


View QuoteBuy now

Fast response from our specialists

Why buy from Geneq? - find out more


Single channel, analog gas detector for enclosed parking facilities, recreational facilities, oxygen depletion applications

The LPT is an economical, single sensor, analog transmitter for monitoring toxic gases non-hazardous, non-explosion proof rated commercial and light industrial applications. This basic transmitter is designed to be part of a fixed system with a Controller for applications such as car parks, vehicle repair, aquatic centers, ice rinks and oxygen depletion applications. It features a two-wire loop power, three-wire VDC or four-wire VAC power, 4 - 20 mA linear output signal, thermal resetting fuses, temperature compensation, and visual LED indication for power and fault conditions, all in a RoHS compliant package. Comes standard with a water / dust tight, corrosion resistant ABS / polycarbonate enclosure with a hinged, secured door. With the optional splash guard installed, the enclosure is IP54 rated and ideal for use in water spray or wash down applications.

Automated calibration and other maintenance procedures are simple and easily performed in the field. For parking garage applications, our proprietary Calibration Extending Firmware (CEF) takes into account the aging of the sensors so that less frequent calibrations are acceptable in non-critical applications.

Features

  • Single channel
  • Linear 4 - 20 mA output signal
  • 2-wire loop, 3-wire VDC or 4-wire VAC power
  • Standard water / dust tight, corrosion resistant enclosure (drip proof)
  • IP54 rated with optional splash guard installed

Model

LPT-TCO
Single channel, electrochemical carbon monoxide (CO) sensor (0 - 200 ppm range),LED indicator, 4 - 20 mA output, two-wire / three-wire / four-wire VAC power, sensor CEF, water / dust tight enclosure

Target Gas

Gas SensorsCarbon monoxide (CO),Nitrogen dioxide (NO2),Chlorine (Cl2),Oxygen (O2),Sulphur dioxide (SO2)
 

Mechanical

EnclosureABS / Polycarbonate, corrosion resistance
Copper coated interior to reduce RF interference
IP54 rated with optional splash guard installed
Weight200 g / 0.44 lbs
Size127 x 127 x 53 mm / 5.0 x 5.0 x 2.1 inches
 

User Interface

DisplaySingle color status LED
 

Input/Output

OutputLinear 4 - 20 mA
Maximum 216 Ω load
(wiring plus termination resistor) at 16 VDC
Maximum 316 Ω load
(wiring plus termination resistor) at 12 VAC
 

Electrical

Power Requirement2-wire mode: 16 - 30 VDC, 1 W, Class 2
3-wire mode: 16 - 30 VDC, 1 W, Class 2
4-wire mode: 12 - 27 VAC, 50-60 Hz, 1 VA, Class 2
Current Draw25 mA @ 24 VDC (max)
WiringVDC 2-conductor 18 AWG stranded, shielded
VDC 3-conductor 18 AWG stranded, shielded
VAC 4-conductor 18 AWG stranded, shielded
FusesThermal, resetting
 

Environmental

Operating Temperature-20°C to 40°C (-4°F to 104°F)
Operating Humidity15 - 90% RH non-condensing
 

Certifications

Conforms toCSA-C22.2 No. 205-M1983 (R2009),UL508 (Edition 17):2007
EMC Directive 2004/108/EC, EN 50270:2006, Type 1, EN61010
FCC. This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
RoHS compliant circuit boards