Air Velocity Transducer
- TSI - 8455 - 8465 - 8475
For air velocity measurements in research and development labs, manufacturing processes, and other applications.
The 8455, 8465, and 8475 Air Velocity Transducers are ideal for both temporary and permanent installations for air velocity measurements in research and development labs, manufacturing processes, and other applications.
The full–scale range, signal output, and time constant are user selectable and can be easily changed to meet the needs of your application.
Applications |
• Comfort and draft studies • Critical environment installations (e.g., clean rooms and hospitals) • Diffuser design analysis • Monitoring drying processes • Monitoring air flows in tunnels and subways • Used as a standard in wind tunnels and calibration facilities • Environmental monitoring in greenhouses and IAQ applications • General engineering applications |
General Purpose (8455)
- Protected probe tip
- Rugged ceramic sensor
- Wide range of measurement applications
- Fast response time
- Windowless (8465)
- Less flow blockage
- Ideal for measuring in confined spaces
- Fast response time
- Omnidirectional (8475)
- Omnidirectional probe tip
- Accurate at low velocities from 10 to 100 ft/min (0.05 to 0.5 m/s)
- Ideal for unknown or varying flow direction
|
Specifications - Models 8455, 8465, 8475
Temperature Range
Probe length
All models contain on-board electronics and calibration curves that provide a linear signal output. This linear signal is sent out as either a current (mA) or a voltage (V) signal, allowing output to a variety of data loggers or data acquisition systems. In addition, the current and voltage output ranges are user-selectable for your convenience. | |
Accuracy | |
8455 ±2.0% of reading1, ±0.5% of full scale of selected range 8465 ±2.0% of reading1, ±0.5% of full scale of selected range 8475 ±3.0% of reading2, ±1.0% of full scale of selected range | |
Field Selectable Range | |
8455 and 8465 | 25 ft/min to 200, 250, 300, 400, 500, 750, 1,000, 1,250, 1,500, 2,000, 2,500, 3,000, 4,000, 5,000, 7,500, 10,000 ft/min (0.125 m/s to 1.0, 1.25, 1.50, 2.0, 2.5, 3.0, 4.0, 5.0, 7.5, 10.0, 12.5, 15.0, 20.0, 25.0, 30.0, 40.0, 50.0 m/s) |
8475 | 10 ft/min to 100, 125, 150, 200, 250, 300, 400, 500 ft/min (0.05 m/s to 0.5, 0.75, 1.0, 1.25, 1.50, 2.0, 2.5 m/s) |
Repeatability | |
8455 and 8465 | <±1.0% of reading3 |
8475 | N/A |
Response to Flow | |
8455 and 8465 | 0.2 sec.4 |
8475 | 5 sec.5 |
Compensation | 32 to 140°F (0 to 60°C) |
Operating (electronics | 32 to 200°F (0 to 93°C) |
Operating (sensor) | 32 to 200°F (0 to 93°C) |
Storage | 32 to 200°F (0 to 93°C) |
Resolution (minimum) | |
0.07% of selected full scale | |
Input Power | |
11-30 VDC or 18-38 VAC, 350 mA max6 | |
Output | |
Impedance | Voltage mode: less than 1 ohm, 20 mA max source current |
Resistance | Current mode: 500 ohms maximum load |
Signal | Field selectable 0–5V, 0–10V, 0–20, 2–10V, mA, 4–20 mA |
Time Constant | Field selectable 0.05 to 10 seconds |
3 in., 6 in., 9 in., 12 in. (7.5 cm, 15 cm, 22.5 cm, or 30 cm) |
8455/8465 | 8475 | |
Range | 25-10,000 fpm (0.127- 50.8 m/s),selectable | 10-500 fpm (0.051- 2.54 m/s),selectable |
Accuracy | ±(2% of reading at 64.4- 82.4°F (18-28°C) + 0.5% of full scale of selected range) | ±(3% of reading at 68.0- 82.4°F (20-26°C) +1% of full scale of selected range) |
Response time | 0.2 seconds | 5.0 seconds |
Input power | 350 m, 11-30 VDC or 18-28 VAC, A maximum | |
1 From 64.4 to 82.4°F (18 to 28°C),outside this range and within temperature compensation range add 0.4% per °F (0.2% per °C). 2 From 68 to 78.8°F (20 to 26°C),outside this range and within temperature compensation range add 0.9% per °F (0.5% per °C). Directed sensitivity of the Model 8475 is a +5%/-20% of reading +0/-10 ft/min (+0/-0.05 m/s) over 270° solid angle regardless of flow direction. 3 Standard deviation based on one minute average from 100 to 1,000 fpm (0.5 to 5.0 m/s). 4 For 63% of final value, tested at 1,500 fpm (7.5 m/s). 5 For 63% of final value, tested at 500 fpm (2.5 m/s). 6 Input voltage must be maintained within specifications at the transducer. |