Détecteur de gaz et contrôleur à un canal
Voir la soumission
Réponse rapide par nos spécialistes
Avantages de faire affaire avec Geneq - en savoir plus
The SCC Self Contained Controller combines toxic and/or combustible gas detection with basic control functionality for non-hazardous, non-explosion rated, commercial and light industrial applications.
The SCC is available in one or two channel configurations for monitoring toxic and/or combustible gas types by means of an internal electrochemical Carbon monoxide (CO) or Nitrogen dioxide (NO2) sensor and one of three ESH-A remote catalytic combustible sensors used to detect Hydrogen (H2),Propane (C3H8) or Methane (CH4). Monitoring of CO or NO2 may also be achieved remotely by combining the SCC with a 4-20 mA transmitter such as the LPT-TCO or LPT-END. The SCC also features two alarm level line voltage relays with field configurable time delays and trigger levels, a field selectable internal audible alarm and an LED panel indicating power, channel alarm status and fault conditions. Automated calibration and other maintenance procedures are simple and easily performed in the field, and our proprietary Calibration Extending Firmware (CEF) takes into account the aging of the toxic gas sensors so that less frequent calibrations are required in less-critical applications such as parking garages.
Features:
- Single or dual channel operation
- Internal or remote sensors
- LED indicators for Power, CH1, CH2 and Fault
- Two 5-amp SPDT dry contact relays
- Internal audible alarm
- Optional 4 - 20 mA input (replaces remote combustible sensor)
- Standard water / dust tight, corrosion resistant enclosure (drip proof);
- IP54 rated with optional splash guard installed.
- Six conduit entry ports
- Thermal resetting fuse
- RoHS compliant circuit boards
Applications:
- Parking Garages/Car Parks
- Vehicle Repair Shops
- Battery Charging Rooms
- Buildings on Landfill Sites
Specificatons:
Gas Type | |
Carbon Monoxide (CO) Nitrogen Dioxide (NO2) Hydrogen (H2) Methane (CH4) Propane (C3H8) | |
Sensors | |
Carbon Monoxide (CO) Sensor | |
Type: | Electrochemical |
Range: | 0 - 200 ppm |
Sensor Response Time (T90): | 60 seconds |
Operating Temperature: | -20°C to 50°C (-4°F to 122°F) |
Operating Humidity: | 5 - 95% RH non-condensing |
Operating Pressure: | 80 - 120 kPa |
Resolution: | 0.5 ppm |
Repeatability: | < 2% of signal |
Maximum Zero Shift: | N/A |
Clean Air Output Drift: | < 10 ppm equivalent per year |
Expected Life Span: | 6+ years in air (under normal conditions) |
Calibration: | Every 6 months or once a year (depending on application) |
Cross Sensitivity: | H2S @ 20 ppm = < 0.1 ppm |
NO2 @ 10 ppm = < 0.1 ppm | |
Cl2 @ 10 ppm = < 0.1 ppm | |
NO @ 50 ppm = < 5 ppm | |
SO2 @ 20 ppm = < 0.1 ppm | |
H2 @ 20°C (68°F) @ 400 ppm = < 60 ppm | |
C2H4 @ 400 ppm = < 25 ppm | |
NH3 @ 20 ppm = < 0.01 ppm | |
Nitrogen Dioxide (NO2) Sensor | |
Type: | Electrochemical |
Range: | 0 - 10 ppm |
Response Time (T90): | < 30 seconds |
Operating Temperature: | -20°C to 50°C (-4°F to 122°F) |
Operating Humidity: | 15 - 90% RH non-condensing |
Operating Pressure: | Atmospheric ± 10% |
Resolution: | 0.02 ppm |
Repeatability: | < 2% of signal |
Maximum Zero Shift: | ± 0.2 ppm equivalent |
Clean Air Output Drift: | < 2% signal loss / month |
Expected Life Span: | 5 to 6 years in air (under normal conditions) |
Calibration: | Every 6 months or once a year (depending on application) |
Cross Sensitivity: | H2S @ 20 ppm = < -40 ppm |
Cl2 @ 10 ppm = 100 ppm | |
NO @ 50 ppm = < 0.5 ppm | |
SO2 @ 20 ppm = < -2.5 ppm | |
CO @ 400 ppm = < 0.1 ppm | |
H2 @ 400 ppm = < 0.1 ppm | |
C2H4 @ 50 ppm = < 0.1 ppm | |
NH3 @ 20 ppm = < 0.1 ppm | |
CO2 @ 5% volume = < 0.1 ppm | |
Combustibles (CH4, H2, C3H8 ) Remote Sensor | |
Type: | Catalytic |
Range: | 0 - 50% LEL |
Response Time (T90): | < 12 seconds from 0 - 50% LEL |
Operating Temperature: | -10°C to 40°C (14°F to 104°F) |
Operating Humidity: | 20 - 90% RH non-condensing |
Resolution: | 1% LEL |
Accuracy: | No data available |
Long Term Drift: | No data available |
Expected Life Span: | 5 years in air (under normal conditions) |
Calibration: | Every 6 months or once a year (depending on application) |
Cross Sensitivity: | Any combustible gas |
Mechanical | |
Enclosure | ABS / Polycarbonate, rated UL94-5VA |
Weight | 600 g (1.4 lbs) |
Size | 10.0” x 8.6” x 4.3” (254 mm x 218 mm x 109 mm) |
Electrical | |
Power Requirement | Low Voltage: 16 - 30 VDC or 12 - 28 VAC, 10 W, Class 2 |
Line Voltage | 90 – 240 VAC, 50 -60 Hz |
Wiring | 24VDC or 24VAC two-conductor shielded 18 awg stranded within conduit VAC three-conductor shielded 18 awg stranded within conduit |
Fuse | Automatic resetting thermal |
Output | |
Low Voltage: 400 mA @ 24 VDC | |
User Interface | |
LED Indicators: LED Panel indicating "POWER". "CH 1" state, "CH 2" state and "FAULT" | |
Environmental | |
Operating Temperature: -20°C to 50°C (-4°F to 122°F) Humidity: 15 - 90% RH non-condensing | |
Certifications | |
Conforms to: CSA-C22.2 No. 205-M1983 (R2009) UL508 (Edition 17):2007 Conforms to: EMC Directive 2004/108/EC EN 50270:2006, Type 1, EN61010 Conforms to: FCC. This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. |
On est là pour vous aider!
min 10 ch